  3. Will a sprinkler head operate in a ‘dead’ air space where there is no air circulation and not easy to access. The head has a 74°C fusible link with a 57°C cover plate.

Will a sprinkler head operate in a ‘dead’ air space where there is no air circulation and not easy to access. The head has a 74°C fusible link with a 57°C cover plate.

Sprinkler heads in ‘dead’, hard to access spaces could be problematic because they are not easy to inspect or could be inadvertently overlooked. BS EN 12845 Sprinkler Rules makes a reference to unventilated concealed spaces in paragraph 14.4 but does not mention the accessibility of the space.

It states the following: ‘In unventilated concealed spaces it may be necessary to install sprinklers with a higher operating temperature, up to 93°C or 100°C. Sprinkler heads in such spaces will operate if the temperature exceeds their normal operating temperature’.